A valve positioner that has drifted out of calibration does not announce itself. The controller asks for 50% open, the valve settles somewhere else, and the loop compensates by hunting, overshooting, or wearing the valve faster than it should. Calibration is what brings the valve's actual position back in line with the signal the control system sends.
This guide explains how HART-capable electronic valve positioners work, why calibration matters, and a practical step-by-step procedure you can adapt to your plant's own instructions.
An electronic valve positioner receives the control signal and drives the actuator so that the valve reaches the commanded position, then holds it there against process forces. It is the link between what the control system wants and what the valve actually does, which is why its accuracy directly affects process control.
HART (Highway Addressable Remote Transducer) is a widely used digital protocol in the process industry. It superimposes a digital signal on the standard 4-20 mA analog signal, so the analog process variable and digital information travel on the same pair of wires at the same time.
HART communication is bidirectional. It lets technicians configure the positioner, monitor its status, and read diagnostics without disconnecting the loop, which is what makes HART positioners faster to calibrate and troubleshoot than purely analog devices.
Calibration ensures that the positioner's output, the valve travel, corresponds accurately to its input signal. A correctly calibrated positioner responds predictably to control signals, which supports process efficiency, product quality, and safety. Note that some HART positioners have specific operating or calibration modes, so always check the manufacturer's instructions before starting.
A documenting process calibrator with built-in HART communication can source the mA signal, communicate with the positioner, and record the results in one instrument. The Additel 227 Multifunction Process Calibrator is available in a HART version (ADT227-HART) with a built-in HART communicator and DD library, and in an intrinsically safe version, the ADT227Ex.
Highway Addressable Remote Transducer, a digital protocol that superimposes digital communication on the 4-20 mA analog signal.
No. HART communication is bidirectional and runs on the same wires as the analog signal, so configuration, monitoring, and diagnostics can be done with the loop connected.
A HART communicator or a HART-capable process calibrator, a stable air supply, and a way to record as-found and as-left results. A documenting calibrator such as the Additel 227 combines these functions.
The most common cause is insufficient loop resistance. HART typically needs a resistor in the loop, commonly 250 Ω.
Datasheets and technical documents are available on the Additel 227 product page and across the Additel portfolio.
If you are reviewing calibration procedures for HART positioners, or choosing tools for your valve population, we are happy to talk it through. Write to us at sales@avtekconsulting.com.